MGCG Marine Power Cable
Applications
Marine shipboard power cables are used for power systems of cargo ships, Passenger vessels and Special-purpose vessels. For fixed installations on ships and offshore-units in all locations and open deck. The good screening qualities of the copper braid also reduce radio interferences and electrical influences to electronic installation. The cables meet the flame test requirement for bunched cables acc. to IEC 60332-3-22 and IEEE45-18.13, and perform to the SOLAS requirements. All cable materials are free of halogens. This design ensures that non corrosive and low toxic gases are emitted in case of fire. Therefore, these cables are especially suitable for the installation on passenger ships.
Cable Construction
1.Conductor:Annealed Stranded Bare Copper,Class 2
2. Insulation: HEPR (Crosslinked Hard grade Ethylene Propylene)
3.Filler or Tape
4.Armour:Separator tape,Bare copper braid,Separator tape
5.Sheath:Cross linked polychloroprene rubber
Standards
International: IEC 60092-351;IEC 60092-353; IEC 60092-359;IEC 60332-3-22
National:DIN 89158/98
Electrical Characteristics
1.Rated Voltage Uo/U(Um):600/1000V
2.Test Voltage:3500V
Usage Characteristics
Minimum installation temperature
-10 °C
Minimum operating temperature
-35 °C
Short-circuit max. conductor temperature
250 °C
Max. conductor temperature in service
85 °C
Rated Voltage Uo/U (Um)
0.6/1 kV
Test voltage
3500 V
Flame retardant
IEC 60332-3 Cat. A
Smoke density
IEC 61034
Electro magnetic interference resistance
Yes
Gases corrosivity
IEC 60754-2
Gases toxicity
No toxicity to IEC 60754-1
Standard
DIN VDE and IEC
Minimum Internal Bending Radius
1.For overall diameter of cables≤25mm 4×cable diameter
2.For overall diameter of cables>25mm 6×cable diameter