Ship Electrical Fire Damper
1. Product Introduction:
Usually it is open, the angle of blade is adjustable at the range of 0 degree to 90 degrees manually, once fire occurs, the gas temperature of duct arrives at 70 degrees, and then the fuse protector will be fused and the damper will close under the pull of spring. Compared with the ordinary fire proof damper, it also can be closed by DC24V electrical control. It is applied to the pipeline of smoke extraction which needs fireproofing. It can isolate smoke’s leaking and stop the fire spreading.
2. Configuration Options:
Features
Shape
Round
User defined
Rectangle
User defined
Explosion-proof Requirements
Explosion-proof
For use in hazardous areas, containing explosive gases
Non-explosion proof
It is installed on the air duct of the ventilation and air-conditioning system with fire protection requirements.
Material
Carbon steel
Higher hardness and better wear resistance can be obtained after heat treatment. The hardness in the annealed state is very moderate, and it also has good machinability. Raw materials are very common, simple and easy to obtain, and the production cost is relatively low.
Fire Resistance Rating
A0/A15/A30/A60
User defined
Control Unit
Electric Actuator
It can be manually operated on-site and can be controlled remotely.
Control Mode
Local/Remote/Central Control
User defined
Level of Protection
IP54/IP66
User defined
Valve Body Colour
Red(standard)
User defined
3. Specific Difference Between Us and Other Suppliers:
Comparison
Product Picture of other low quality supplier
Product Picture of our factory
Other low quality supplier
Consequence
Our Factory
Consequence
The thickness of the damper shell does not meet the requirements
The casing is prone to breakage
The thickness selection of the damper shell The regulations of each classification society are consistent with the SLOAS requirements
The shell meets the requirements, and the damper can be used for a longer time
The fire rating does not meet the requirements
It is easy to leave a safety hazard
Select as required
Product use more assured, longer service life
The installation accuracy of the connecting rod between the baffles is not enough
As a result, when the fire damper is closed, the shutter still cannot be completely closed.
The connecting rod between the baffles is installed with high precision
When the fire damper is closed, the shutter can be fully closed.
Air leakage does not meet the requirements
Excessive air leakage from fire dampers will cause major safety hazards
Airtight performance is selected according to requirements
The air leakage meets the requirements, and the product is safer to use
4. Features:
Using galvanized steel as material to make sure good insulation performance, fire & corrosion resistance.
Duration, long service life.
Easy installation.
The flange is bended directly by the frame.
The valve size and color can be customized according to customer's requirements.
5. Outline Drawing:
6. When arranging fire dampers, pay attention to:
1. The height of the installation location is generally controlled at about 1.5m. If the height exceeds 2m, rope traction should be used.
2. When using a wire zipper, the length is required to be less than 6m, the number of bends is less than 3, the bending radius is greater than 300mm, and the steel pipe is used as a sheath to protect the rope.
3. The fire damper is arranged in the dangerous area, the remote control solenoid valve should be placed in the safe area together with the control box, and the remote control device is 1.5m away from the ground.
4. The control of the fire damper (marine fire damper) on the kitchen exhaust duct should be interlocked with the release of carbon dioxide, and the control box should be placed near the kitchen door.
5. The tuyere baffle of the emergency generator room should be interlocked with the start of the generator diesel engine. According to ISO requirements, usually the fire damper in the emergency generator room adopts the form of non-failure closing.