JIS C3410 LV Power and Lighting Cable - Marine Power Cable - Hi-sea

JIS C3410 LV Power and Lighting Cable



JIS C3410 LV Power and Lighting Cable

Application:
This Cable can be applied in Marine&Offshore and various ships, ship repair and oil platforms and other offshore buildings control device and general electric lighting,machinery and equipment of factories and mines are also equally applicable.


JISC 3410 LV Power Cable Standards:
- Design guide : JIS C 3410(1999/2010)

- Flame retardant : IEC 60332-1 & IEC 60332-3 Category A (FA-Type)

- Cold bend/impact : CSA 22.2 No. 03 (-35 ) (Cold Type)

- Max. conductor temperature : 85℃


JISC 3410 LV Power Cable Model:
0.6/1kV SPYC, SPYCY, FA-SPYC, FA-SPYCY 0.6/1kV SPYCB, SPYCBY, FA-SPYCB, FA-SPYCBY 0.6/1kV D(T,F,5,6,10)PY, FA-D(T,F,5,6,10)PY 0.6/1kV D(T,F,5,6,10)PYC, FA-D(T,F,5,6,10)PYC 0.6/1kV D(T,F,5,6,10)PYCY, FA-D(T,F,5,6,10)PYCY 0.6/1kV D(T)PYE, D(T)PYCE, D(T)PYCYE


JISC 3410 MV power Cable Construction:


MV power and lighting Cable Diagram:

Conductor T(S) Tinned annealed stranded copper, class 2 according to IEC 60228
Conductor screen
Semi-conducting compound
Insulation P 85°C EPR as per IEC 60092-351
Insulation screen
Semi-conducting compound /Tinned copper tape
Filler
Non-hygroscopic material (If necessary)
Bedding Y PVC,ST2 type
Armor C (CB) Galvanized steel wire braid(-C TYPE) or copper alloy wire braid(-CB TYPE)
Sheath Y PVC ST2 type
Core identification
3C Red, Yellow, Blue
Outer sheath color
Red













Installations Recommendations:
Minimum Cable Bending Radius
The internal radius of cable bends which are not subjected to movements by expansion, is not to be less than : 6 times the external diameter of cable Cable which are subjected to movements by expansion and the high voltage cable are to be bent to a form of at least 12 times cable diameter.
Installations Temperature
Minimum recommended temperature of installations : -10°C Ship wiring cable with PVC sheath -20°C Elastomeric on/off shore cables
Installations Pulling Force
The cable pulling force can be estimated, as a maximum limit :5Kp per mm2 conductor area in the cable.Additional tension will be supplied from the braid and the insulation and sheathing compound.