JIS C3410 Armored Control Cable
JIS C3410 Control Cable application:
This product is suitable for all kinds of ships and offshore oil platforms and other control structures and electrical transmission .
JIS C3410 Control Cable Service condition:
Voltage rating: 250V
Maximum conductor temperature: 85°C
JIS C3410 Control Cable Applied Standard:
-JISC 3410-1999 -IEC 60092-350 -IEC 60332-1 -IEC 60332-3 Cat.AF(for FA-type)
JIS C3410 Control Cable Construction:
Conductor | M | Tinned annealed stranded copper, class 2 according to IEC 60228 |
Insulation | P | 85°C EPR as per JIS C 3401 |
Cabling |
|
Insulated conductors shall be cabled. Flame retardant & non-hygroscopic fillers may be used |
Bedding | Y | PVC as per JIS C 3401 |
Armor | C | Galvanized steel wire braid |
Sheath | Y | PVC as per JIS C 3401 |
Core identification |
|
Black No. on white insulation /Black No. on white insulation, G/Y |
Outer sheath color |
|
Black |
Minimum cable bending radius:
The internal radius of cable bends which are not subjected to movements by expansion, is not to be less than : 6 times the external diameter of cable
Cable which are subjected to movements by expansion and the high voltage cable are to be bent to a form of at least 12 times cable diameter.
Installations temperature:
Minimum recommended temperature of installations :
-10°C Ship wiring cable with PVC sheath
-20°C Elastomeric on/off shore cables
Installations pulling force:
The cable pulling force can be estimated, as a maximum limit :5Kp per mm2 conductor area in the cable.
Additional tension will be supplied from the braid and the insulation and sheathing compound.
JIS C3410 Control Cable Parameter:
<
No. of cores | Conductor | Thick. of insulation | Thick. of bedding | (FA-) MPY | ||||
Size | Construction | O.D | Nom. overall dia | Tolerance | Cable Weight | |||
mm² | No./mm | mm | mm | mm | mm | mm | kg/km | |
2 | 1 | 7/0.43 | 1.29 | 0.7 | 1.1 | 8.7 | 0.4 | 85 |
4 | 1 | 7/0.43 | 1.29 | 0.7 | 1.1 | 9.9 | 0.4 | 125 |
7 | 1 | 7/0.43 | 1.29 | 0.7 | 1.2 | 11.9 | 0.5 | 190 |
12 | 1 | 7/0.43 | 1.29 | 0.7 | 1.3 | 15.5 | 0.7 | 315 |
19 | 1 | 7/0.43 | 1.29 | 0.7 | 1.4 | 18.3 | 0.8 | 465 |
27 | 1 | 7/0.43 | 1.29 | 0.7 | 1.6 | 22.1 | 0.9 | 665 |
37 | 1 | 7/0.43 | 1.29 | 0.7 | 1.7 | 24.8 | 1 | 870 |
44 | 1 | 7/0.43 | 1.29 | 0.7 | 1.8 | 28 | 1.2 | 1160 |
77 | 1 | 7/0.43 | 1.29 | 0.7 | 2.1 | 35.9 | 1.5 | 1790 |
No. of cores | Conductor | Thick. of insulation | Thick. of bedding | Dia. of steel wire | Thick. of covering | (FA-) MPYCY | ||||
Size | Construction | O.D | Nom. overall dia | Tolerance | Cable Weight | |||||
mm² | No./mm | mm | mm | mm | mm | mm | mm | mm | kg/km | |
2 | 1 | 7/0.43 | 1.29 | 0.7 | 1.1 | 0.3 | 0.9 | 12 | 0.5 | 205 |
4 | 1 | 7/0.43 | 1.29 | 0.7 | 1.1 | 0.3 | 0.9 | 13.2 | 0.5 | 260 |
7 | 1 | 7/0.43 | 1.29 | 0.7 | 1.2 | 0.3 | 0.9 | 15.2 | 0.6 | 350 |
12 | 1 | 7/0.43 | 1.29 | 0.7 | 1.3 | 0.3 | 1 | 19 | 0.8 | 530 |
19 | 1 | 7/0.43 | 1.29 | 0.7 | 1.4 | 0.3 | 1.1 | 22 | 0.9 | 720 |
27 | 1 | 7/0.43 | 1.29 | 0.7 | 1.6 | 0.3 | 1.2 | 26 | 1 | 980 |
37 | 1 | 7/0.43 | 1.29 | 0.7 | 1.7 | 0.3 | 1.3 | 28.9 | 1.2 | 1240 |
44 | 1 | 7/0.43 | 1.29 | 0.7 | 1.8 | 0.3 | 1.3 | 32.1 | 1.3 | 1470 |
77 | 1 | 7/0.43 | 1.29 | 0.7 | 2.1 | 0.4 | 1.5 | 41.1 | 1.6 | 2470 |