Design instructions
(1) The zero plane position in the pool, the size and location of the outlet pipe, sewage discharge and emptying are all determined by the demand side according to the actual situation.
(2) The water pressure at the zero plane of the tower body should be 0.08-0.15MPa.
(3) Water quality requirements: no large mechanical impurities, the particle size of mechanical impurities is less than 10 mm.
(4) The above parameters are only for reference in the selection of industrial medium-temperature cooling towers. The design of low-temperature and high-temperature cooling towers should be adjusted appropriately.
(1) Dry bulb temperature: θ= 31.5 ℃, wet bulb temperature τ= 28 ℃, atmospheric pressure P = 9.94 *104Pa
(2) Influent temperature t1=43 ℃, effluent temperature t2=33 ℃
Model
Cooling water volume (m³/h)
Fan
Water collector (㎡)
Influent main (DN)
Standard point noise dB(A)
Tower size
model
Air flow
(Q×104m³/h)
power
(KW)
H1
(mm)
H2
(mm)
H3
(mm)
a
(mm)
b
(mm)
WBBF-50
50
LYD-16A
5.9
3
6.3
80
60
1000
3300
600
2500
2500
WBBF -100
100
LYD-24A
8.4
5.5
10.2
150
63
1000
3300
700
3200
3200
WBBF -150
150
LYD-28A
11.8
7.5
16
150
63
1100
3300
700
4000
4000
WBBF -200
200
LYD-34A
16.8
7.5
19.4
200
65
1200
3300
700
4400
4400
WBBF -250
250
LYD-34B
18.74
7.5
25
200
66
1200
3300
700
5000
5000
WBBF -300
300
LYD-38A
21.2
11
31.4
250
66
1300
3300
800
5600
5600
WBBF -350
350
LYD-38B
23.53
11
33.6
250
66
1300
3300
800
5800
5800
WBBF -400
400
LYD-42A
30.22
15
36
250
66
1400
3300
900
6000
6000
WBBF -500
500
LYD-50A
35.32
18.5
43.6
300
68
1500
4000
1200
6600
6600
WBBF -600
600
LYD-50B
40.8
22
53.3
350
68
1600
4000
1500
7300
7300
WBBF -700
700
LYD-60A
49.35
22
70.6
350
69
1800
4000
1500
8400
8400
WBBF -800
800
LYD-60B
54.5
30
81
400
70
2000
4000
1500
9000
9000