JIS C3410 Common Screened Telephone Cable
JIS C 3410 Overall shield telephone cable application:
JIS C 3410 Overall shield telephone cable is intended for Instrument circuit upto 250V, instrument safe systems. Fixed installation for instrument, communication, control and alarm system in both explosion risk and safe areas, general purposes.
JIS C 3410 Overall shield telephone cable model:
250V TTYS, FA- TTYS 250V TTYCS, FA- TTYCS 250V TTYCYS, FA- TTYCYS
JIS C 3410 Overall shield telephone cable standards:
- Design guide : JIS C 3410(1999/2010)
- Flame retardant :IEC 60332-1 & IEC 60332-3 Category A (FA-Type)
- Cold bend/impact : CSA 22.2 No. 03 (-35 ) (Cold Type)
- Max. conductor temperature : 60
JIS C 3410 Overall shield telephone cable construction:
JIS C3410 Common Screened Telephone Cable Diagram:
Classification | Code | Construction details |
Conductor | TT | Tinned Copper Wire JIS C3410 |
Insulation | Y | PVC as per JIS C 3410 |
Common Shield | S | Tinned Copper Wire |
Armor | C | Galvanized steel wire braided |
|
CB | Tinned copper wire braided |
Paint |
|
The white paint should be painted uniformly |
Covering | Y | PVC as per JIS C 3410 |
|
|
Color: Black |
Recommendations Minimum cable bending radius:
The internal radius of cable bends which are not subjected to movements by expansion, is not to be less than : 6 times the external diameter of cable
Cable which are subjected to movements by expansion and the high voltage cable are to be bent to a form of at least 12 times cable diameter.
Installations temperature:
Minimum recommended temperature of installations :
-10°C Ship wiring cable with PVC sheath
-20°C Elastomeric on/off shore cables
Installations pulling force:
The cable pulling force can be estimated, as a maximum limit :5Kp per mm2 conductor area in the cable.
Additional tension will be supplied from the braid and the insulation and sheathing compound.