CJ86 EMC Fire Resistant Armored Power and Control Cable
Applications:
This product is used in ships,petrol platforms and offshore buildings for power,light and control systems,usually used for fixed installation in most areas and open deck in ships.Design to meet requirements for improved EMC screening properties.If the cable is exposed to direct sun light protective covering or cable with black outer sheath is recommended.
Constructions:
1.Conductor Stranded copper wire 1.0mm² to 10mm² Class 2
Stranded copper wire 16mm² to 240mm² Class 5(Flexible)
2.Insulation Mica tape XLPE
3.Bedding Separate tape
4.Screen Copper tape,covering 100%
5. Amore Copper wire braided,covering 90%
6.Sheath Thermoplastic Polyolefine(SHF1),On requesting Thermosetting Polyolefine(SHF2) standard colour black, other colours on request.
Applied Standards:
Design | IEC 60092-353 |
Conductor | IEC 60228 Class 2,Class 5 |
Insulation | IEC 60092-351 |
Sheath | IEC 60092-359 |
Flame-retardant | IEC 60332-1-2 -test for single insulated wire and cable IEC 60332-3-22 -test for bunched wires and cables, category A |
Fire -resistant | IEC 60331-1 and IEC 60331-2 |
Halogen-free | IEC 60754 series |
Smoke emission | IEC 61034 series |
Transfer Impedance | IEC 61196-1 (typical value 26dB over 1mΩ/m at 100MHz [20mΩ/m]) |
Service Conditions:
1.Rated Voltage:AC 0,6/1kV (1,2kV) DC 0,9/1,5kV (if voltage to earth does not exceed 0,9kV)
2.long time working temperature 90℃
3.Minimum recommended installation temperature -15 °C
Lowest operation temperature -40 °C
4.flexible cables for mobile devices,the other cables are fixed laying cable bending radius while laying is as below
Cable Structure | Cable Outer Diameter | Minimum Bending Radius |
Metal Braided Armored | 6D | |
Non Armored | D≤25 | 4D |
D>25 |
6D |