CAW Marine Indirect Evaporative Cooling Air Condition
Overview
1. CAW marine air condition is one of the air conditioning systems that shall be used together with water chilling unit. It is featured by compact structure , low vibration, low noise and easy installation.
2. CAW marine air condition mainly consists of air filter, air heat exchange,fan, motor and electrical control cabinet, etc. In addition, flow control valve station can be provided in full sets according to the requirement of user.
Installation in Shipyard
1. Pay attention not to damage any component of the tube system and the unit during lifting. The body is made of thin steel plates, hangers shall be used for lifting. Wooden plate shall be used as protection pad for wall face in order to protect the body from damage.
2. See General Drawing or Overall Dimension Drawing for the dimension of bolt hole in the base of water chilling unit.
3. Shock insulation measures shall be considered at the base of water chilling unit.
3. Crelative valves and thermometer necessary for water inlet and outlet pipes of condenser shall be installed by shipyard, while water pressure gauge and water pressure controller have been properly installed by the manufacturer.
4. Connect feed cable conductor to the power line terminals in the electrical control cabinet, and lay the alarm wire, etc.
Main Technical Parameters
CAW-23 | CAW-35 | CAW-47 | CAW-58 | CAW-70 | CAW-82 | CAW-93 | CAW-105 | ||
Cooling Capacity | Kw | 23 | 35 | 47 | 58 | 70 | 82 | 93 | 105 |
Heating Capacity | Kw | 37 | 40 | 54 | 70 | 82 | 93 | 105 | 116 |
Regenerating Medium | 7℃ Cooling Fresh Water | ||||||||
Heating Medium | ≥45℃ Heating Fresh Water/0.3 ~ 0.4Mpa Water | ||||||||
Heating Steam Consumption |
kg/h | 60 | 80 | 99 | 120 | 140 | 159 | 182 | 198 |
Humidifying Steam Consumption |
kg/h | 9 | 12 | 16 | 19 | 22 | 25 | 28 | 30 |
Air Flow | m3/h | 3200 | 3700 | 4200 | 5000 | 6200 | 7200 | 8200 | 9000 |
Fan Motor Power | Kw | 2.2 | 3.2 | 5.5 | 5.5 | 7.5 | 11 | 11 | 15 |
External Static Pressure |
Pa | 450 | 900 | 900 | 1050 | 1200 | 1500 | 1570 | 1500 |
Cooling(Heating) Water Flow |
m3/h | 4 | 6 | 8 | 10 | 12 | 14 | 16 | 18 |
Cooling Water Press.Drop |
KPa | 26 | 30 | 35 | 41 | 45 | 50 | 56 | 60 |
Power Supply | AC380V 3Ph 50Hz /AC440V 3Ph 60Hz | ||||||||
Weight | kg | ~700 | ~800 | ~900 | ~950 | ~1000 | ~1050 | ~1150 | ~1200 |
CAW-116 | CAW-151 | CAW-175 | CAW-186 | CAW-210 | CAW-232 | CAW-250 | CAW-291 | ||
Cooling Capacity | Kw | 116 | 151 | 175 | 186 | 210 | 232 | 250 | 291 |
Heating Capacity | Kw | 134 | 167 | 186 | 215 | 232 | 250 | 291 | 335 |
Regenerating Medium | 7℃ Cooling Fresh Water | ||||||||
Heating Medium | ≥45℃ Heating Fresh Water/0.3 ~ 0.4Mpa Water | ||||||||
Heating Steam Consumption |
kg/h | 228 | 284 | 317 | 370 | 400 | 430 | 500 | 580 |
Humidifying Steam Consumption |
kg/h | 35 | 44 | 49 | 64 | 68 | 80 | 88 | 95 |
Air Flow | m3/h | 10500 | 13100 | 15100 | 16000 | 18000 | 20000 | 22000 | 25000 |
Fan Motor Power | Kw | 15 | 15 | 22.5 | 30 | 37 | 37 | 45 | 45 |
External Static Pressure |
Pa | 1500 | 1600 | 1800 | 1800 | 1800 | 1800 | 1900 | 1900 |
Cooling(Heating) Water Flow |
m3/h | 20 | 26 | 30 | 32 | 38 | 40 | 43 | 50 |
Cooling Water Press.Drop |
KPa | 66 | 82 | 89 | 100 | 110 | 120 | 130 | 140 |
Power Supply | AC380V 3Ph 50Hz /AC440V 3Ph 60Hz | ||||||||
Weight | kg | ~1450 | ~1700 | ~1800 | ~2500 | ~2700 | ~2900 | ~3100 | ~3200 |